REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This page includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvements, specifications, weights and dimensions are subject to change without notice.

General notes

1. All connections 100 mm and smaller are MPT. Connections 125 mm and larger are beveled-for-welding.
2. Make up, overflow, suction and drain connections can be provided on end opposite to that shown; consult your BAC representative.
3. Models 1012-09 thru 1012-10, 1018-09 thru 1018-10, 1212-09 thru 1212-12 and 1218-09 thru 1218-12 are shipped in two sections per cell. The top section heights are for model 1012-09 thru 1012-10 and 1212-09 thru 1212-12, 2501 mm. For models 1018-09 thru 1018-10 and 1218-09 thru 1218-12, 2562 mm.

S1500E cooling tower performance at standard conditions

Last update: 26/12/2024

S15E 1012-06

S150E 1012

1. Water in; 2. Water out; 3. Make up; 4. Overflow ND80; 5. Drain ND50; 6. Access door.

Model Weights (kg) Dimensions (mm) Air Flow (m³/s) Fan Motor (kW) Fluid Inlet ND (mm) Fluid Outlet ND (mm) Make Up ND (mm)
Oper. Weight (kg) Ship. Weight(kg) Heaviest Section (kg) L W H
S15E 1012-06HE 5103 2436 2436 3651 2997 3091 24.0 (2x) 4.0 (1x) 200 (1x) 200 (1x) 40
S15E 1012-06JE 5148 2481 2481 3651 2997 3091 27.0 (2x) 5.5 (1x) 200 (1x) 200 (1x) 40
S15E 1012-06KE 5161 2494 2494 3651 2997 3091 29.0 (2x) 7.5 (1x) 200 (1x) 200 (1x) 40