REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This page includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvement, specifications, weights and dimensions are subject to change without notice.

General notes

1. Access door is always opposite to inlet connection end.
2. Alternative inlet/outlet and tower configurations are available.
3. Nominal outlet connection size provided.
4. Actual outlet sized to match flow.
5. Models RCT 2218-1 and 2129-1 have direct drive motors.
6. Models RCT 2218-2 and 2129-2 have direct drive motors.
7. Triple fan units are not available with common FRP basin. Only for installation on concrete basin.

Last update: 23/12/2024

RCT 2142-3 - 2320-3

RCT_2118-3_2320-3

1. Water inlet; 2. Fan motor; 3. Concrete basin (by others).

Model Weights (kg) Dimensions (mm) Air Flow (m³/s) Fan Motor (kW) Fluid Inlet ND (mm)
Oper. Weight (kg) Ship. Weight(kg) Heaviest Section (kg) L W H
RCT 2142-3 10125 3750 1250 7732 2589 3555 55.6 (3x) 5.5 (3x) 150
RCT 2156-3 10125 3750 1250 7732 2589 3555 61.2 (3x) 7.5 (3x) 150
RCT 2183-3 12375 4650 1550 8646 2894 3671 71.6 (3x) 7.5 (3x) 200
RCT 2208-3 12375 4650 1550 8646 2894 3671 81.6 (3x) 11.0 (3x) 200
RCT 2238-3 14550 5400 1800 9560 3198 3931 93.6 (3x) 11.0 (3x) 200
RCT 2262-3 14550 5400 1800 9560 3198 3931 102.6 (3x) 15.0 (3x) 200
RCT 2299-3 17100 6300 2100 10471 3499 4124 117.1 (3x) 15.0 (3x) 200
RCT 2320-3 17100 6300 2100 10471 3499 4124 125.3 (3x) 18.5 (3x) 200