REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This page includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvement, specifications, weights and dimensions are subject to change without notice.

General notes

1. Standard refrigerant in- and outlet connection sizes are ND100. Consult your local BAC representative for locations. Refrigerant connections are closed and coils are filled with an inert gas.
2. Unit height is indicative. For precise value refer to certified print.
3. Shipping/operating weights indicated are for units without accessories such as sound attenuators, discharge hoods, etc. Consult factory certified prints to obtain weight additions and the heaviest section to be lifted. Operating weights shown in the tables is based on total unit weight, weight of refrigerant operating charge and basin filled to overflow level.
4. Drawings show the standard right hand arrangement (air inlet side on the right when facing the connection end). Left hand arrangement can be supplied upon request.


 

Last update: 24/11/2021

PLC2 XXX-0409E-L

PLC2-0409-STD-12R%20-%20Web%20-%202021.jpg

1. Refrigerant in ND100; 2. Refrigerant out ND100; 3. Make up ND40; 4. Overflow ND80; 5. Drain ND50; 6. Bleed ND25; 7. Treated Water In ND20; 8. Access door.

Model Weights (kg) Dimensions (mm) Air Flow (m³/s) Fan Motor (kW) Water Flow (l/s) Pump Motor (kW) R717 charge (kg)
Oper. Weight (kg) Ship. Weight(kg) Heaviest Section (kg) L W H
PLC2 093-0409E-L 2462 1617 898 2799 1207 3070 14.7 (3x) 4.05 8.9 (1x) 1.5 27.0
PLC2 0117-0409E-L 2645 1787 898 2799 1207 3305 14.0 (3x) 4.05 8.9 (1x) 1.5 40.0
PLC2 0138-0409E-L 2822 1952 1054 2799 1207 3540 13.4 (3x) 4.05 8.9 (1x) 1.5 52.0
PLC2 0158-0409E-L 3003 2120 1222 2799 1207 3775 12.9 (3x) 4.05 8.9 (1x) 1.5 64.0
PLC2 0164-0409E-L 3134 2239 1340 2799 1207 3790 12.5 (3x) 4.05 8.9 (1x) 1.5 77.0