REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This page includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvement, specifications, weights and dimensions are subject to change without notice.

General notes

1. Standard refrigerant connection sizes are ND 100 BSP MPT inlet and outlet (for models VXC 14 through 28 refrigerant connection sizes are ND 80 BSP MPT), consult your local BAC representative for size and location. Other connection sizes are available on special order. Refrigerant connections are standard bevelled for welding.
2. Make up, overflow, suction, drain connection and access door can be provided on side opposite to that shown; consult your BAC representative.
3. Unit height is indicative, for precise value refer to certified print.
4. Shipping/operating weights indicated are for units without accessories such as sound attenuators, discharge hoods, etc. Consult factory certified prints to obtain weight additions and the heaviest section to be lifted.
5. The drawing units with only one spray pump show the standard right hand arrangement has the air inlet side on the right when facing the connection end . Left hand can be furnished by special order.
6. Coil, overflow, make-up and spray water connections are always located on the same end of the unit. For double pump units an additional overflow connection will be installed on the other end of the unit.
7. On model VXC 14 through VXC 135 access doors are located at the opposite of the air inlet side, ensure sufficient space for entry when positioning these units.
8. For indoor applications of evaporative condensers, the room may be used as a plenum with ductwork attached to the discharge only. If inlet ductwork is required, an enclosed fan section must be specified; consult your BAC representative for details.
9. Fan kW is at 0 Pa ESP. To operate against external static pressure up to 125 Pa, increase each fan motor one size.
10. Refrigerant charge listed is R717 operating change. To determine operating charge of R 22 refrigerant, multiply by: 1,93. For R134A, multiply by : 1.98.
11. For dry operation, standard motors must be increased one size to avoid motor overloading. Extended surface coils are available to vastly increase dry capacity without motor size increase. Consult your Bac Representative for selection and pricing.
12. Models VXC 357-454, VXC 562-380, VXC 495-516 and VXC 725-804 have only 1 coil casing section and one or two fan motors. Fan cycling results in only on-off operation. On these units all fans need to operate simultaneously.
13. Models VXC 714-907, VXC 1124-1360, VXC 990-1032 and VXC 1430-1608 have 2 coils casing sections and one or two fan motors per coil casing section. Fan cycling results in only-off operation. On these units all fans need to operate simultaneously per coil casing section.

Last update: 23/12/2024

VXC S288-S1010

VXC_S288_S1010

1. Refrigerant in ND100; 2. Refrigerant out ND100; Make up ND50; 4. Overflow ND80; 5. Drain ND50; 6. Access.

 

Model Weights (kg) Dimensions (mm) Air Flow (m³/s) Fan Motor (kW) Water Flow (l/s) Pump Motor (kW) R717 charge (kg)
Oper. Weight (kg) Ship. Weight(kg) Heaviest Section (kg) L W H
VXC S288 7600 5525 3850 3550 2397 4248 22.8 (1x) 18.5 25.2 (1x) 2.2 164.0
VXC S300 7630 5555 3850 3550 2397 4248 24.2 (1x) 22.0 25.2 (1x) 2.2 164.0
VXC S328 7705 5630 3850 3550 2397 4248 26.7 (1x) 30.0 25.2 (1x) 2.2 164.0
VXC S350 8320 6180 4470 3550 2397 4483 26.2 (1x) 30.0 25.2 (1x) 2.2 196.0
VXC S403 10225 7170 4715 5385 2397 4013 36.6 (1x) 30.0 38.5 (1x) 4.0 198.0
VXC S429 10285 7230 4715 5385 2397 4013 38.9 (1x) 37.0 38.5 (1x) 4.0 198.0
VXC S455 11270 8125 5710 5385 2397 4248 34.9 (1x) 30.0 38.5 (1x) 4.0 246.0
VXC S482 11320 8175 5710 5385 2397 4248 37.5 (1x) 37.0 38.5 (1x) 4.0 246.0
VXC S504 12500 9260 6690 5385 2397 4483 36.6 (1x) 37.0 38.5 (1x) 4.0 294.0
VXC S576 15120 10880 3840 7226 2397 4248 45.6 (2x) 18.5 50.4 (2x) 2.2 328.0
VXC S600 15220 10980 3840 7226 2397 4248 48.4 (2x) 22.0 50.4 (2x) 2.2 328.0
VXC S656 15400 11100 3840 7226 2397 4248 53.4 (2x) 30.0 50.4 (2x) 2.2 328.0
VXC S700 16655 12355 4470 7226 2397 4483 52.4 (2x) 30.0 50.4 (2x) 2.2 392.0
VXC S806 20555 14415 5120 10903 2397 4013 73.2 (2x) 30.0 77.0 (2x) 4.0 396.0
VXC S858 20755 14615 5120 10903 2397 4013 77.8 (2x) 37.0 77.0 (2x) 4.0 396.0
VXC S910 22570 16420 5710 10903 2397 4248 69.8 (2x) 30.0 77.0 (2x) 4.0 492.0
VXC S964 22770 16550 5710 10903 2397 4248 75.0 (2x) 37.0 77.0 (2x) 4.0 492.0
VXC S1010 25035 18505 6690 10903 2397 4483 73.2 (2x) 37.0 77.0 (2x) 4.0 588.0